Gas Detection Sample Draw System

Class 1, Division 2 Approved for Sampling from a Class 1 Division 1 Area

Gas Detection Sample Draw System

Hazardous Area Approved, Gas Detection Sample Draw System

For use with Sensidyne Fixed Gas Detectors

  • Class 1, Division 2 Rated for Sampling from a Class 1 Division 1 Area

  • FM Listed for NFPA 820 Compliance

  • Pumped or Air Aspirated Versions

  • Flow Sensor with Relay that Fails Safe

  • Internal Power Switch and Flow Adjust

  • 24 VDC Power Source for Gas Detectors

  • Fiberglass Wall-mount Enclosure

The Sensidyne Sample Draw System samples air from remote locations pulling a sample to gas detection transmitter(s) and is offered as a diaphragm pumped or an air operated aspirator unit. It is FM approved for placement in a Class I, Division 2 Hazardous (Classified) area to sample from a Class I, Division 1 Hazardous (Classified) area, Groups C and D. A Division 2 approval eliminates the need for flame arrestors and reduces related maintenance caused by dirt and moisture.

Flow rate is easily adjustable and a rotameter is provided for visual indication of flow. A fail-safe flow switch can de-actuate the relay and provide a signal on loss of flow or power. A two-way valve permits the application of calibration standards to the gas sensor(s) for routine preventative maintenance.

 

The Sample Draw System is housed in a wall-mount fiberglass enclosure and rated NEMA 3R. The system power supply is capable of operating the pump and multiple in-line transmitters, enabling up to four gas sensors placed downstream of the sample for monitoring different gases. This integral power source enhances capabilities for remote applications such as pumping stations, large laboratories, and gas hoods while significantly reducing installation costs.

PRODUCT SPECIFICATIONS


Enclosure

Material

NEMA 3R Fiberglass wall mount with two 3/4” conduit entries

Dimensions:

11” (H) X 10” (W) X 6.375” (D) (27.9cm X 25.4cm X 16.2cm)

Weight:

6.6 lbs (3.0 kg)

Temperature:

-4° to 104°F (-20° to 40°C)

Humidity:

5-95% RH, non-condensing for indoor or outdoor locations.

Indicators and Controls

External:

Flowmeter, green power LED and red fault/low flow LED

Internal:

On-Off switch, voltage out adjust and flow rate adjust

Outputs:

Two 24 VDC power terminals, SPDT fault/low flow relay contact

Power In/Out:

85–264 VAC, 47-63 Hz, 1.2 Amps; 24 VDC, 1.1 Amp max.

Approvals

Hazloc

FM approved for Class 1, Division 2 Groups C & D Rated for Sampling from a Class 1 Division 1 Area Groups C & D

DC Supply:

UL60950-1, UL508, UL1310(3), EN60950-1, CE Mark

Pump:

Diaphragm type rated at 1.0 lpm @ 40” H2O at pressurized leak rate of < 1.0 inch wc drop in 5 seconds at 25 inches wc

Wetted parts:

Polycarbonate, Neoprene, Tygon 2075, Silicone Silastic, 304/316ss, Buna-N, Brass, PVC, Glass, Acrylic and User Tubing

Caution

Do not use for Acid gases such as Cl2, ClO2, HCl, HF, HCN, NH3, NO2, SO2 and others since the PPM gases are absorbed by the tubing, moisture and various wetted parts slowing or completely eliminating response to the target gas. Do not attempt to use below freezing without heat tracing and a means to keep the system above 32⁰ F (0⁰ C). Excessive condensation will occur when sampling from a higher to a lower temperature.

Ordering Information

Pumped Sample Draw with 24 VDC power supply

821-0231-01

Aspirated Sample Draw with 24 VDC power supply

821-0232-01

Close Nipple 1/8 NPT fitting

550-1010-01

Coalescing filter and Close Nipple 1/8 NPT

821-0233-01

Filename Filesize
/chroot/home/a70c8823/public_html/Support Library/gas-detection/Sample Draw
360-0155-01rF Sample Draw Manual - Pumped.pdf 1.15 MB
360-0155-02rE Sample Draw - Aspirated.pdf 949.55 kB
Sensidyne_Sample-Draw-Datasheet_rD.pdf 734.51 kB