Calibration Ensures Compliance — and Peace of Mind.
Infrequent calibration of sensors could lead to inaccurate gas detection readings and possibly result in the failure to detect gas leaks resulting in an unprotected zone.
Sensidyne gas detectors are tested and calibrated at the factory with the target gas prior to shipment. To maintain safe operation, all gas detectors require a zero check and gas verification upon installation and at regular intervals in accordance with instructions in the User Manual.
Failure to calibrate and operate Sensidyne gas detectors in accordance with their User Manuals could result in product malfunction.
Factory Recommended Procedures
After installation and stabilization of the gas detector, qualified personnel must verify calibration by applying zero and span gases. This procedure should be performed at initial commissioning and then repeated 30 and 60 days thereafter, with deviations in zero and span recorded. The gas detector should then be calibrated at intervals dependent upon the application, but no less often than once every 90 days, except for infrared sensors which have a maximum 180 day calibration interval.
Sensors must always be calibrated upon installation 1 and after a gas alarm.
For further information on industry standards for sensor calibration, please refer to ISA 60079-29-2 (12.13.02)-2012 Explosive Atmospheres - Part 29-2: Gas Detectors - Selection, Installation, Use and Maintenance of Detectors for Flammable Gases and Oxygen, published by the ISA.
Support and Assistance
For questions regarding Sensidyne recommended calibration procedures, or to learn about the Sensor Calibration Exchange Program,
» Submit Service RMA Request Form
» Keep a Calibrated Sensor at Our Factory
Contact us to explore further:
800-451-9444 x783
+1 727-530-3602 x783
Email Gas Detection Service
1 Calibration upon installation is not required for sensors provided as part of the Sensidyne Sensor Calibration Exchange Program, or calibrated on site through the transportable calibration feature.